中国电机工程学报 2009, 29(16) 49-55 DOI:
ISSN: 0258-8013 CN: 11-2107/TM |
|
|
|
|
本期目录 |
下期目录 |
过刊浏览 |
高级检索
[打印本页]
[关闭] |
|
| 继电保护、通信及自动化 |
|
|
变压器外部故障切除后差动保护误动原因及防止对策 |
|
|
谷君,郑涛,黄少锋,王增平 |
|
|
电力系统保护与动态安全监控教育部重点实验室(华北电力大学) |
|
|
摘要:
针对近年来相继出现的变压器差动保护在外部故障切除后发生误动的现象,研究了电流互感器(current transformer,CT)饱和以及Y/D接线变压器补偿方式对差动保护的影响。通过理论分析与仿真研究发现,变压器外部故障切除后CT发生局部暂态饱和时,由于只传变工频周期分量,误差很小,不足以引起差动保护误动。如果变压器一侧CT发生超饱和,而另一侧CT能正确传变时,由于两侧CT传变特性不一致可能引起差动保护误动;另外变压器Y侧电流的相位补偿也容易引起差动保护误动。通过对保护误动时的动作轨迹的分析,提出利用分区延时法以防止差动保护误动。通过大量的仿真实验,证明该方法既能保证差动保护在内部故障时的速动性,也能保证在外部故障切除后不误动。 |
|
|
关键词:
变压器差动保护
外部故障
CT超饱和
相位补偿
延时法
|
|
|
Mal-operation of Transformer Differential Protection After Removal of
External Fault and Countermeasure
|
|
|
GU Jun, ZHENG Tao, HUANG Shao-feng, WANG Zeng-ping |
|
|
Key Laboratory of Power System Protection and Dynamic Security Monitoring and Control (North China Electric Power University), Ministry of Education |
|
|
Abstract:
Mal-operation of the transformer differential protection will occasionally take place after the removal of the external fault. The physical phenomena of the current transformer (CT) saturation and the phase compensation scheme of the transformer with wye-delta connection are studied in this paper. Based on the theoretical analysis and simulation research, this paper points out that CT partial transient saturation after the removal of transformer external fault only transforms the fundamental frequency component with a small transformation error, and won’t result in the mal-operation of differential protection. If CT on one side of the transformer becomes ultra-saturated and CT on the other side is in the linear region, the inconsistent transformation of CT will result in the mal-operation of differential protection. In addition, the phase compensation of the transformer wye-side current will also result in the mal-operation of differential protection. Through the analysis of the mal-operation point, a method of different time delays in different areas is presented to prevent the differential protection from mal-operation. Simulation results show that the new method will guarantee the fast operation of the differential protection in the case of an internal fault while avoiding the mal-operation after removal of the external faults. |
|
|
Keywords:
transformer differential protection
external fault
current transformer ultra-saturation
phase compensation
time delay method
|
|
|
收稿日期 2008-09-03 修回日期 2008-12-22 网络版发布日期 2009-06-09 |
|
|
DOI: |
|
|
基金项目:
国家自然科学基金项目(50607006,50777016);高等学校博士点专项科研基金(20060079009)。 |
|
|
通讯作者: 谷君 |
|
|
作者简介: |
|
作者Email: |
|
|
| 参考文献: |
|
| 本刊中的类似文章 |
| 1.李肖博 肖仕武 刘万顺 郑涛.基于形态滤波的变压器电流相关保护方案[J]. 中国电机工程学报, 2006,26(6): 8-13 |
| 2.翁汉琍 林湘宁.变压器差动保护误动原因的复杂电磁暂态分析[J]. 中国电机工程学报, 2009,29(13): 65-71 |
| 3.郑涛 谷君 黄少锋 王增平.基于数学形态梯度的变压器转换性故障识别新判据[J]. 中国电机工程学报, 2008,28(22): 75-80 |
| 4.李晓华 柳焕章 尹项根 陈德树.新型双K值差动保护研究[J]. 中国电机工程学报, 2007,27(25): 49-55 |
| 5.韩小涛 李伟 尹项根 陈德树.应用电子式电流互感器的变压器差动保护研究[J]. 中国电机工程学报, 2007,27(4): 47-53 |
| 6.邵德军 尹项根 张哲 陈德树 金明亮.基于基波幅值增量的变压器和应涌流识别方法[J]. 中国电机工程学报, 2010,30(10): 77-83 |
| 7.杜姣 陆于平 朱国防.幅值相位双判据变压器差动保护算法[J]. 中国电机工程学报, 2010,30(16): 79-85 |
|
| Copyright by 中国电机工程学报 |