中国电机工程学报 2007, 27(33) 53-58  DOI:      ISSN: 0258-8013 CN: 11-2107/TM

本期目录 | 下期目录 | 过刊浏览 | 高级检索                                                            [打印本页]   [关闭]
电机电工
扩展功能
本文信息
Supporting info
PDF(361KB)
[HTML全文]
参考文献[PDF]
参考文献
服务与反馈
把本文推荐给朋友
加入我的书架
加入引用管理器
引用本文
Email Alert
文章反馈
浏览反馈信息
本文关键词相关文章
正直流电晕
起始电压
离子电流
气压
湿度
本文作者相关文章
惠建峰
PubMed
Article by
正直流电晕特性随气压和湿度变化的研究
惠建峰 关志成 王黎明 麻敏华 李秋玮
清华大学深圳研究生院 清华大学深圳研究生院 清华大学深圳研究生院 清华大学深圳研究生院 清华大学深圳研究生院
摘要: 电晕是输电线路设计和运行中面临的重要问题之一。文中通过实验测量和模拟计算,得到了不同气压湿度下的正直流电晕起始电压和电晕离子电流。计算结果和实验结果吻合较好。电晕起始电压随气压下降、湿度升高而减小,其主要原因分别为有效电离系数增大导致的电离区域的扩大和高场强区域内碰撞电离能力的增强。当直流电压和电晕起始电压的比值一定时,电晕离子电流也随气压下降、湿度升高而减小。电晕离子电流和直流电压、电晕起始电压关系式中的系数C随湿度升高而减小。当气压降低,C随湿度下降的斜率增大。湿度一定时,C和相对空气密度近似成反比。正离子迁移率是影响C变化的主要因素。
关键词 正直流电晕   起始电压   离子电流   气压   湿度  
Research on Variation of Positive DC Corona Characteristics With Air Pressure and Humidity
Abstract: Corona is one of important problems in the design and operation of transmission lines. It was obtained through experiment and simulation that positive DC corona inception voltage and corona ion current under different air pressure and humidity conditions. Calculated results are in good agreement with experimental ones. Corona inception voltage decreases as air pressure is lowered or humidity is raised. It is mainly due to the enlargement of ionization zone and strengthening of collisional ionization intensity respectively as a result of the increase of effective ionization coefficient. Corona ion current also decreases with the fall of pressure or rise of humidity when the ratio of DC voltage to corona inception voltage is equal. The coefficient C, in the relationship among corona ion current, DC voltage and corona inception voltage, declines with the increase of humidity. The decreased rate of C with humidity becomes larger as pressure is reduced. An approximately inversely proportional relationship exists between C and relative air density at constant humidity. The variation of C is principally associated with the positive ion mobility.
Keywords: positive DC corona   inception voltage   ion current   pressure   humidity  
收稿日期 2006-08-27 修回日期 1900-01-01 网络版发布日期  
DOI:
基金项目:

通讯作者: 惠建峰
作者简介:
作者Email: huijf02@mails.tsinghua.edu.cn;huijf02@gmail.com

参考文献:
本刊中的类似文章
1.蒋兴良,林锐,胡琴,张志劲,胡建林.直流正极性下绞线电晕起始特性及影响因素分析[J]. 中国电机工程学报, 2009,29(34): 108-114

Copyright by 中国电机工程学报